Visualisation method for assessment of frost formation on air cooler
DOI:
https://doi.org/10.36119/15.2020.5.2Keywords:
refrigeration, air cooler, frosting, thermal degradation, visualization method, heat transferAbstract
Finned tube heat exchangers are widely used in heating, ventilation, air conditioning and refrigeration. In the case of exchangers operating as air coolers, frost formation occurs, which generally strongly deteriorates the efficiency of heat transfer by creating additional thermal resistance and causing additional pressure loss. The paper provides with the analysis of the effect of frosting process on the operation of the air cooler using the method proposed by the authors using observations synchronised with thermal measurements of air cooler. On the basis of long-term tests of the air cooler operating in the vegetables cold storage chamber the influence of frosting process was assessed, among others on cooling capacity, bypass factor, and thermal resistance. In the analysed case, frosting reduced the cooling capacity by up to 40%.
Downloads
References
Downloads
Published
Issue
Section
Categories
License

This work is licensed under a Creative Commons Attribution 4.0 International License.
Authors retain copyright and grant the journal the right of first publication, with the work simultaneously licensed under a Creative Commons Attribution 4.0 International License, which permits others to share the work with appropriate acknowledgment of the authorship and initial publication in this journal.