Operational efficiency of a steam boiler plant

Authors

  • Janusz Bujak Uniwersytet Technologiczno-Przyrodniczy w Bydgoszczy, Bydgoszcz Author
  • Ryszard Okoński Uniwersytet Technologiczno-Przyrodniczy w Bydgoszczy, Bydgoszcz Author
  • Sebastian Majkowski PPM PROMONT Bujak Sp. z o.o. – Sp. K., Bydgoszcz Author

DOI:

https://doi.org/10.36119/15.2020.11.2

Keywords:

steam boiler plant, shell boilers, heat balance

Abstract

The article presents the results of experimental studies on the operational efficiency of a steam boiler house. The installation of a steam boiler house consists of a set of shell boilers and a technological installation. The article discusses the issues related to the thermal operational efficiency of a steam boiler house with steam shell boilers fired by gaseous and liquid fuels. The results of tests of the operational efficiency of a steam boiler in its operating conditions are presented. The research was carried out for 18 months in the steam boiler room of the Provincial Hospital. Test results obtained at the real object were compared to research results according to PN-EN 12953-11. The tests proved that the actual thermal operational efficiency is lower than that determined by the standard. This is due to the fact that under real conditions the amount of components responsible for its loss is larger than the norm for its calculation.

Downloads

Download data is not yet available.

References

Downloads

Published

2020-11-30

How to Cite

Bujak, J., Okoński, R., & Majkowski, S. (2020). Operational efficiency of a steam boiler plant. Instal, 11, 14-18. https://doi.org/10.36119/15.2020.11.2