Operational uptime as performance-based measure of natural ventilation in an open car park
DOI:
https://doi.org/10.36119/15.2025.1.3Keywords:
natural ventilation, open car park, CFD, smoke control, heat controlAbstract
192 CFD simulations of an open car park fire under wind conditions were conducted to assess the efficiency of natural ventilation. In the majority of considered cases, natural ventilation was ineffective. The influence of wind direction on ventilation performance was observed. Using historical wind data, the percentage of time during which the outcomes were acceptable was estimated. This value was termed operational uptime and amounted to 87.62% for a fire with a heat release rate of 1.4 MW; 40.30% for 4.0 MW; 36.39% for 6.0 MW; and 14.24% for 8.8 MW.
Downloads
References
https://news.sky.com/story/luton-airport-car-park-fire-due-to-vehicle-fault-as-man-arrested-12990789; dostęp z 02.10.2024;
K. Storesund, C. Sesseng, R. Mikalsen, O.A. Holmvaag, A. Steen-Hansen, RISE-report 2020:91 – Evaluation of fire in Stavanger air-port car park 7 January 2020, 2020;
Merseyside Fire & Rescue Service, “King Docks car park fire,” 2018;
R. Ramponi, B. Blocken, CFD simulation of cross-ventilation flow for different isolated building configurations: Validation with wind tunnel measurements and analysis of physical and numerical diffusion effects, J. Wind Eng. Ind. Aerodyn. 104–106 (2012) 408–418. doi:10.1016/j.jweia.2012.02.005;
Downloads
Published
License

This work is licensed under a Creative Commons Attribution 4.0 International License.
Authors retain copyright and grant the journal the right of first publication, with the work simultaneously licensed under a Creative Commons Attribution 4.0 International License, which permits others to share the work with appropriate acknowledgment of the authorship and initial publication in this journal.